When you need experienced help in developing a repair proposal,
generator schedule, a second opinion for expensive repairs or a risk
assessment of your generators, please call AC Generator Consultants.
AC Generator Consultants will help you calculate, operate,
supervise, plan and execute generator core loop or ring tests to
approximately 85% of the rated flux. This simple test requires
detailed planning to quickly execute the connections to 4160V or
2380V power supply and breaker and to then pull the heavy turns
through the generator core.
AC Generator Consultants can provide support and execute lower
voltage core tests or repairs such as EL CID (digital or analog),
acid etching repairs, core grinding or polishing, insertion of
nonmetallic shims, opening core packages with mechanical spreaders
and the addition of low surface tension air cure epoxies such as red
eye or weeping epoxy.
We do belly band tightening, core flange nut tightening and knife
testing of your generator core. Core ring testing or core loop
testing require temperature ramp, soak time, convergence and
divergence of temperature differential at hot spots.
AC Generator
Consultants 770.262.4906
Generator Stator Fault Analysis Risk | Generator Field Rotor
Analysis Risk
AC Generator Consultants – The Choice for Quality!
Generator Stator Fault Analysis Risk
| Generator Field Rotor Analysis Risk